DSP MLTPWR/5KVA/ONLINE W/BATT

DSP MLTPWR/5KVA/ONLINE W/BATT
DSP MLTPWR/5KVA/ONLINE W/BATT
(голяма снимка)
0.00 лв. / 0.00 с ДДС

бр.

не е налично - не е налично
(продукта отсъства от пазара)

  - в количката 0 бр.
    (от този продукт)

Пазарска количка - до тук 0.00 лв. / 0.00 €
(общо продукти - 0 бр.)




към страницата на DSP MLTPWR/5KVA/ONLINE W/BATT


Описание на DSP MLTPWR/5KVA/ONLINE W/BATT:



INFORM DSP MULTIPOWER DSPMP 1105

Product type
Power module + batteries

Power
5 kVA

Input
Phase Configuration 1Ph+N+PE
Nominal Voltage 220V/230V
Minumum Voltage 160V
Maximum Voltage 280V
Frequency 45-65 Hz
Power Factor 0,99

Output
Power Factor 0.8
Phase Configuration 1Ph+N+PE
Nominal Voltage 220V / 230V (adjustable)
Nominal Current at 220V 23A
Wave Form Pure Sine Wave
Total Harmonic Distortion at 100% linear load <3%
At 100% Non-Linear Load <5%
Frequency 50Hz or 60Hz (adjustable)
Frequency Tolerance (free running) ±0,2%
Frequency Regulation ±1Hz; ±3Hz
Statik Voltage Regulation (0%-100% load) <1%
Crest Factor 3:1
Transfer Time 0sec
Overload (100% to 150%) 2.5 min
Overload (>150%) Transfer to By Pass
Total Efficiency ≥ 92%
Greenmode Efficiency ≥ 97%
Output Connection Terminals
Outlets (Optional) External Socket Box (2pcs SCHUKO, 4pcs IEC Outlets)

Battery
Type Maintenance-Free lead acid batteries
Recharge Time 4-6h up to 90%
Voltage 240VDC
Quantity per string 20pcs
Cold start Present

Display
LED+LCD Display
Line Mode, Back up Mode, Eco Mode, Bypass Supply, Battery Low,
Battery Bad/Disconnect, Overload, UPS Fault, Interruption during transfer
LCD Display Input Voltage, Input Frequency, Output Voltage, Output Frequency, Load%,
Battery Voltage, Internal Temperature
Self Diagnostics Upon Power On, Front Panel Setting and Through Software Control,
24h routine Check

Protection
Overload Protection
(w/simulated thermal tripping I-T Curve) Inverter Supply: 105%-150% for 160 secods~2 cycles before switching bypass.
Bypass supply: 105%-200% for 500 secods ~ 8 cycles before stopping supply load.
Short Circuit Protection Switch Off Immediately
Other Protection Overheat, Battery Low

Communication interface
Interface (Communication Ports) Standard RS232 port and optional RS485, Internal SNMP, Dry Contact Cards
Monitoring and Management Software Standard

Environment
Operating Temperature 0° C ... + 40° C
Proposed Temp. To Extend Battery Life 20 - 25° C
Humidity up to 90% (non-condensing)
Audible Noise at 1m <50 dB
Protection Class IP 20

Physical Specifications (Tower Position)
Net Weight (power module) 25kg
Net Weight (with internal batteries) 55kg
Dimensions (mm) (HxWxD)-power module 440x88x680
Dimensions (mm) (HxWxD)-w/battery vers 440x176x680

Standards
Standards EN62040-1-1 (safety); EN62040-2 (EMC); EN62040-3 (performance); EN60950-1