FORTRON GALLEON 2KVA ONLINE UPS
- Model
Galleon 2K
- Capacity
2000 VA/ 1600 W
- Input
Voltage Range
Low Line Transfer 160 VAC / 140 VAC / 120 VAC / 110 VAC ± 5 % or 80 VAC / 70 VAC / 60 VAC / 50 VAC ± 5 % ( based on load percentage 100% - 80 % / 80 % - 70 % / 70 - 60 % / 60 % - 0)
Low Line Comeback 175 VAC ± 5 % or 85 VAC ± 5 %
H qh Line Transfer 300 VAC ± 5 % or 150 VAC ± 5 %
H gh Line Comeback 290 VAC ± 5 % or 145 VAC ± 5 %
Frequency Range 40 Hz - 70 Hz
Phase Single phase with ground
Power Factor 0.95
- Output
AC Voltage Regulation (Batt. Mode) ±3%
Frequency Range (Synchronized Range) 47.5Hz - 52.5 Hz or 57Hz - 63 Hz
Frequency Range (Batt. Mode) 50 Hz ± 0.25 Hz or 60Hz ± 0.3 Hz
Current Crest Ratio 3:1
Harmonic Distortion 4 % THD (Linear Load) 7 % THD (Non-linear Load)
Transfer Time AC Mode to Batt Mode Zero
Inverter to Bypass 4 ms (Typical)
Waveform (Batt. Mode) Pure Sinewave
- Efficiency
AC Mode 88%
Battery Mode 83%
- Battery
Battery Type 12 V/7 Ah
Numbers 6
Typical Recharge Time 4 hours recover to 90% capacity
Charging Current (max.) 1.0 A
Charging Voltage 82.1VDC±1%
- Indicators
LCD Panel UPS status, Load level. Battery level, Input/Output voltage, Discharge timer, and Fault conditions
- Alarm
Battery Mode Sounding every 4 seconds
Low Battery Sounding every second
Overload Sounding twice every second
Fault Continuously sounding
- Physical
Tower Case
Standard Model Dimension, D x W x H
421 x 190 x 318 mm
Net Weight (kgs) 26
- Environment
Operation Humidity 20-90 % RH @ 0- 40°C (non-condensing)
Noise Level Less than 45dB @ 1 Meter
- Management
Smart RS-232/USB Supports Windows® 98/2000/2003/XP/Vista/2008, Linux, and MAC
www.fsp-group.com